Corrected from:
-
Response of the new version:
-
What happens?
After a communication interruption (e.g. Ethernet plug is disconnected at the Lenze controller c750), logging into the c750 with the PLC Designer is not possible for approx. 2 minutes. First the error message appears:
No connection to the gateway
When the connection to the c750 has been re-established and an attempt is made to go online with the PLC Designer, the error message appears:
Logging in is not possible at the moment. A user is logged in via PLC Designer.
When does the behaviour occur?
The behaviour described above occurs after a brief interruption of the network connection.
Which products are affected?
Cabinet Controller c750
Short-term measures:
After a connection interruption between PLC Designer and c750, do not log in again until 3 minutes have elapsed.
Evaluation / recommendations:
After a connection interruption between PLC Designer and Lenze Controller c750, going online immediately is not possible.