Engineering port: With gateway address 0.0.0.0 the device search does not work (corrected from V01.07.04)

Corrected from:
Servo-Inverter i950 FW:  from V01.07.04
 
Response of the new version:
The device search works even if the gateway address is not set.
 
What happens?
Engineering port: Device search for establishing a connection via Ethernet:
The i950 Servo Inverter is not found via the 'Browse' dialogue in the Lenze engineering tool 'Easy Starter'.

When does the behaviour occur?
  • Manually assign engineering port IP configuration and 
  • Gateway address set under parameter 0x2451:003 = "0.0.0.0", i.e. no gateway used.
Which products are affected?
Servo-Inverter i950 FW
 
Short-term measures / Evaluation / recommendations:
As gateway address, set the same address as the IP address under parameter 0x2451:001.

Automatic Translation

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202100268/1/