Corrected from:
L_TS2P_TechModulesSynchronizingCamming (from V3.24.0)
Update via Easy Package Manager
Response of the new version:
The TM does not report an error when the offset lrSetOffsetMaster is adjusted.
What happens?
The TM L_TS2P_CrossCutter reports the error MasterOutOfCam error (eErrorID = 22025)
When does the behaviour occur?
The cutting mode is set to eCuttingMode= 3 (cutting to a mark (event-driven)) and the offset lrSetOffsetMaster >0 is set.
Which products are affected?
Function module L_TS2P_CrossCutterState from library L_TS2P_TechModulesSynchronizingCamming
Short-term measures:
With the attack point AP07_xSetOffsetSlave = TRUE and AP07_lrSetOffsetSlave > 0, an offset can be specified on the slave side.
Evaluation / recommendations:
The error message is reported at the TM as soon as the x-position is shifted out of the cam plate by the offset lrSetOffsetMaster. Alternatively, an offset on the slave side can be used as described in the short-term measure.
Automatic Translation