L_TS2P_SyncAndCorrection: No warning if tool offset is activated and TP mapping is missing (corrected from V3.24.0)

Corrected from:
Library:  L_TS2P_TechModulesSynchronizingCamming (from V3.24.0)
                      (Update via EASY Package-Manager)

Behaviour of new version:
The error MissedMappingParameterTpTimeStamp(17186) is triggered if the tool offset is active and the bit "xSupportTimeStamp" of the input structure "scTPRecData_ToolSensor" =FALSE.

What happens?
Currently the touchprobe timestamps are not automatically added to the EtherCAT mapping.
This means that no touch probes are transmitted to the technology module.
 
When does the behaviour occur?
The behaviour always occurs when a TM SyncAndCorrection is used on a C5x0 controller. 
 
Which products are affected?
L_TS2P_SyncAndCorrectionBase from library L_TS2PTechMoulesSynchronizingCamming

Short-term measures:
Evaluation / recommendations:

Automatic Translation

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202100035/1/