Corrected from:
L_TP2P_TechModulesProcessFunctions (from V3.24.0)
Update via Easy Package Manager
Response of the new version:
With the FB L_IE1P_ReadActualErrorCode it is possible to read the warnings of the TM L_TP2P_TemperatureControl.
What happens?
Reading warnings of the TM L_TP2P_TemperatureControl with the FB L_IE1P_ReadActualErrorCode does not work.
When does the behaviour occur?
The TM L_TP2P_TemperatureControl is connected with the FB L_IE1P_ReadActualErrorCode. The TM activates a warning that is reported at the output of the TM. FB L_IE1P_ReadActualErrorCode does not display the warning.
Which products are affected?
L_TP2P_TemperatureControlBase from library L_TP2P_TechModulesProcessFunctions.
Short-term measures:
The warning can always be read out in the logbook of the controller or at the output of the TM.
Evaluation / recommendations:
The described error behaviour has no effect on the functionality of the technology module. The active warnings can be read out as described in the short-term measure.
Automatic Translation