Mains failure monitoring: With 230V and 480V mains, the clamps for 400V mains are incorrectly effective (corrected from V01.04.01)

Corrected from:
Servo Inverter i950 FW:   from V01.04.01.1471
 
Response of the new version:
All network classes (0x2540) can now be used without restrictions for power failure monitoring.

  
What happens?
Power failure monitoring: The nominal DC link voltage is used to detect a power failure.
For the mains classes 230V and 480V, with reduced undervoltage threshold (0x2540:1 = 10 and 0x2540:1 = 12), the nominal DC link voltage is incorrectly used for the 400V mains class. As a result, the power failure monitoring does not function correctly.
 
When does the behaviour occur?
Use of the power failure monitoring and
Setting the network classes "230 Veff/reduced LU level [10]" or "480 Veff/reduced LU level [12]" (0x2540:1 = 10 or 0x2540:1 = 12).
 
Which products are affected:
Servo-Inverter i950 FW
 
Short-term measures/ Evaluation/ Recommendations:
Use the network classes without reduced LU threshold (0x2540:1=0 and 0x2540:1=2).

Automatic Translation

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/201900333/1/