PLC-Designer: Save parameter set via device command (0x2022:3) does not work (corrected from V01.05.02)

Corrected from:
Servo Inverter i950 FW from V01.05.02.1788
 
Response of the new version:
Saving parameters via PLC-Designer using the device command (0x2022:3) now works correctly.

 
What happens?
In some cases the device command "Safe User Data" (0x2022:3) is not executed correctly.
The device command is started with 0x2022:3 = On/Start[1] and remains incorrectly at 0x2022:3 = On/Start[1].
Normally the parameter changes automatically to 0x2022:3 = Off/Complete[0] after the saving is finished.

When does the behaviour occur?
PLC-Designer: Saving the parameter set to SD card by means of device command (0x2022:3).
Reproducibility 10-20%.

Which products are affected?
Servo Inverter i950 FW version
 
Short-term measures / Evaluation / Recommendations:  

Use Easy-Starter to save the parameter set.