Status 0x500A:5 following error warning and error is not plausible (corrected from V01.03.07)

Corrected from:
Servo inverter i950 FW  from V01.03.07.1252
 
Response of the new version:
The status bit 16 and status bit 17 are displaying the correct status now.

 
What happens?
The status display of status bit 16 'FollowingError - Warning Active' and status bit 17 'Following Error - Error Active' in the status word 0x500A:5 is swapped:
  • When the current following error (0x500A:57) exceeds the warning threshold Warning threshold 0x500A:55, Following Error - Error Active bit 17 = TRUE
  • If the error threshold (0x500A:56) is exceeded as well, Following Error - Warning Active bit 16 = TRUE
 
When does this behaviour occur?
The behaviour occurs when the following error monitoring function is active:
  • Monitoring enabled   0x500A:54 = TRUE
  • Default control mode 0x500A:90 = 0 or 1: Poscontrol
 
Which products are affected?
Servo inverter i950 FW
 
Short-term measures / Evaluation/recommendations:
The states cannot be diagnosed via bit 16 and bit 17.
The following error monitoring function is not impaired. The monitoring responses are executed as expected.