Corrected from:
Cabinet Controller c520 as of V1.5
Cabinet Controller c550 as of V1.5
Response of the new version:
Exeption handling (TRY, CATCH,...) is supported by Lenze controllers c520 and c550.
During compilation the error message appears:
C0330: Structured exception handling is not supported by your current target.
When does the behaviour occur?
The behavior occurs when IEC commands for exception handling (TRY, CATCH,...) are used in a project for a Lenze controller c520 or c550.
Which products are affected:
Cabinet controller c520 as of V1.0
Cabinet controller c550 as of V1.0
Short-term measures:
Do not use exception handling blocks in your PLC logic for Lenze controller c520 and c550.
Evaluation / Recommendations:
For the Lenze controller c520 and c550 the use of the IEC blocks for exception handling leads to a translation error.