p300: Code 424 (Auto dimming: time) displays no values (corrected from V3.19)

Corrected from:
Panel Controller p300 V3.19
 
Response of the new version:
The "Auto dimming" time can be set via code position 424. The code position shows the correct value after the input.
 
What happens?
The value of code 424 (Auto dimming: time) is not displayed.
After entering a new value, the value returns to 0. 
 
When does this behaviour occur?
The WebConfig is used to change C424.
 
Which products are affected?
Panel Controller p300 (from firmware V3.16.0.106).
 
Short-term measures:
Use the EasyStarter to change the value. After entering the value, here again, the value returns to 0. However, when saving the value directly SAVE button), it will be retained even after switching the mains for the p300. The value must, however, be saved directly after changing it. If necessary, change and save the value several times.