Osilloscope function: status words 0x2831 and 0x2832 cannot be oscillographed correctly (corrected from V02.12.02)
Corrected from:
Servo-Inverter i700, V2: from V02.12.02.12444
Servo-Inverter i700, V1: no repair planned for V1
Response of the new version:
The status words 0x2831 and 0x2832 are now updated every millisecond and can therefore be oscillographed correctly.
Response of the new version:
The parameter storage variables for displaying the status words 0x2831 and 0x2832 are not updated correctly and zero is displayed continuously during oscillography. The associated variable in the parameter storage is only updated when the object is read. If the objects are not "mapped", they are neither read out via PDO nor via parameter communication (SDO). The parameter storage variables are therefore all set to zero.
When does the behaviour occur?
If the status word objects 0x2831 and 0x2832 are not "mapped" and are therefore not transmitted cyclically via PDO.
Which products are affected?
Servo-Inverter i700, V1
Servo-Inverter i700, V2
Short-term measures:
If necessary, extend the PDO mapping by the status word objects to be oscillographed.