Corrected from:
- Inverter Drives 8400 motec V10.00.00
Response of the new version:
When the same values are written, the default settings are no longer loaded for a short time. Thus, downloading parameters can no longer lead to a change of the output levels.
What happens?
When downloading parameters via the Engineer or EasyStarter, the level of the digital outputs may change for a short time. All outputs under C00621/x are affected.
When does this behaviour occur?
When downloading parameters, the outputs are reset to their default settings first and then overwritten with the new values. This may lead to a short-time level change.
Which products are affected?