PLC Designer: When going online, differences are detected in the parameter sets of the i700

Corrected from:
Servo Inverter i700, V1: no fix provided for V1
Servo Inverter i700, V2: PLC Designer: from i700 device description V02.15

Response of the new version:
When going online to the controller, actual value parameters are now excluded from the parameter set comparison. 
Thus only differences in setting parameters are reported, which corresponds to the practical requirement. 
 
What happens?
PLC-Designer: When going online to the controller, differences in the parameter sets are reported, although no setting parameters were changed by the user.
 
When does this behaviour occur?
The behavior occurs when parameter sets have been previously saved with the EasyStarter, per 'Save parameter set in device'.
The differences are detected because the saved parameter set of the i700 also contains parameters for displaying actual values. Actual values, by their nature, always vary somewhat.

Which products are affected?
Servo-Inverter i700, V1
Servo-Inverter i700, V2
 
Short-term measures / Evaluation / Recommendations: 
Reported differences in actual value parameters have no effect on the functionality and can be ignored in this respect.