3241 C controller does not start after restoring a backup (corrected from V3.13.1)
Corrected from: 3241 C controller V3.13.1
Response of the new version:
After restoring a backup on a 3241 C controller, the controller starts immediately.
What happens?
After restoring data from a backup file, the 3241 C controller does not start anymore. The 'Status 1' LED is blinking.
When does this behaviour occur?
The behaviour may occur if a backup created by a 3241 C controller with a firmware version lower than V3.13.1 is restored on a different 3241 C controller.
Which products are affected? All 3241 C controller versions
Short-term measures:
Please contact the Lenze Service.
Evaluation/recommendations:
The controller may no longer start after restoring a backup. This function restriction only affects the 3241 C controller. Using the SD card from an old 3241 C in a new 3241 C, e.g. when replacing devices, is still possible without difficulty.
Taxonomy:
Controller 3241 C
,
Controller 3221 C
,
Controller 3231 C
,
Controller 3251 C
,
Controller 3200 C
AKB-ID:
201600438
Last update:
2023/09/09
Category:
Version Informations