L_TT1P_TablePositioning: Touch probe positioning does not work when using absolute positioning with final speed (corrected from V3.13)

Corrected from:
L_TT1P_TechnologyModules_LM (V3.13.0.7)
 
Response of the new version:
In the case of absolute positioning with final speed, the technology module changes to the correct sequence profile if a touch probe occurs.
 
What happens?
The technology module does not respond to the touch probe.
 
When does this behaviour occur?
A touch probe event is used to change from absolute positioning with final speed (lrFinalVelocity <> 0) to a sequence profile.
 
Which products are affected?
L_TT1P_TablePositioning function block from the L_TT1P_TechnologyModules_LM library (V3.12.0.9 and higher)
 
Short-term measures:
If possible, use relative touch probe positioning or set lrFinalVelocity = 0 for this application.
 

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/201500903/1/