L_MC1P: Homing can only be aborted via the 'MC_Stop' function (corrected from V3.13.0)

Corrected from:
- Library: L_MC1P_MotionControlBasic (FAST Motion) V03.13.00.38
                 (contained in PLC Designer from V03.13.00) 
 
Response of the new version:
When activating other functions such as MC_Halt, MC_MoveAbsolute, etc. the homing function will be aborted now.
 
What happens?
An active homing process can only be aborted via the 'MC_Stop' function.
When activating other functions such as MC_Halt, MC_MoveAbsolute, etc. homing is n o t aborted and the homing state is not left.
 
When does this behaviour occur?
Always.
 
Which products are affected?
- Library: L_MC1P_MotionControlBasic (FAST Motion)
                 (contained in the PLC Designer)
 
Short-term measures:  
Use the MC_Stop function to abort an active homing process.
 
Evaluation/recommendations: