Digital outputs connected to the backplane bus cannot be switched (eliminated from 3200 C V3.6)
Eliminated from: 3200 C controller V3.6
Behaviour of the new version:
Even if only digital I/O 1000 output modules (EPM-S3xx) are connected to the backplane bus of the 3200 C, the outputs are controlled correctly.
What happens? The outputs of a digital I/O 1000 output module connected to the backplane bus of the 3200 C controller cannot be switched by the PLC program.
When does the problem occur? If only digital I/O 1000 output modules (EPM-S3xx) are connected to the backplane bus of the 3200 C controller, the outputs cannot be switched by the PLC program.
Which products are concerned? 3200 C controller V3.3 and higher
Possible diagnostics: None
Short-term measures/recommendations: Additionally connect e.g. a digital I/O 1000 input module to the backplane bus of the controller.
Evaluation: The function restriction occurs if only digital I/O 1000 output modules are connected to the backplane bus of the 3200 C controller.
Taxonomy:
Controller 3221 C
,
Controller 3231 C
,
Controller 3241 C
,
Controller 3251 C
,
Controller 3200 C
AKB-ID:
201301791
Last update:
2023/09/09
Category:
Version Informations