Digital outputs connected to the backplane bus cannot be switched (eliminated from 3200 C V3.6)

Eliminated from:
3200 C controller V3.6
 
Behaviour of the new version:
Even if only digital I/O 1000 output modules (EPM-S3xx) are connected to the backplane bus of the 3200 C, the outputs are controlled correctly.
 
What happens?
The outputs of a digital I/O 1000 output module connected to the backplane bus of the 3200 C controller cannot be switched by the PLC program.

When does the problem occur?
If only digital I/O 1000 output modules (EPM-S3xx) are connected to the backplane bus of the 3200 C controller, the outputs cannot be switched by the PLC program.

Which products are concerned?
3200 C controller V3.3 and higher

Possible diagnostics:
None

Short-term measures/recommendations:
Additionally connect e.g. a digital I/O 1000 input module to the backplane bus of the controller.

Evaluation:
The function restriction occurs if only digital I/O 1000 output modules are connected to the backplane bus of the 3200 C controller.