MCK status displays are not consistent to one another (eliminated in 8400 HighLine from V11.0, TopLine from V02.0)

Eliminated as of:
HighLine with firmware version V11.00
TopLine with firmware version V02.00

Behaviour of the new version?
The level changes of the status signals at the end of a positioning process are carried out in the same computer program cycle.



What happens?
The status displays are not consistent to one another in terms of time. The signal evaluation in the higher-level PLC leads to maloperation.

When does the problem occur?
When the status signals are evaluated.

Which products are affected?
HighLine with firmware version V06.xx
TopLine with firmware version V01.xx

Diagnostics options?
The time-dependent course of the status information can only be evaluated by a control system.

Short-term measures/recommendations?
Smoothing of the status signals in the higher-level control.

Evaluation:
During the commissioning of the application, the data inconsistency is detected.