Downloading parameters with the card module - PR0 error when device sizes differ (eliminated as of OPERATING SYSTEM V8.3)

Eliminated as of:
ECS Application OPERATING SYSTEM  as of V8.3

Behaviour of the new version?
Downloading parameter sets with the card module now functions without errors even if the device sizes differ.



Which products are affected?
ECS Application OPERATING SYSTEM <= V8.0

What happens?
PR0 error is triggered. When the PR0 error message is reset, the Lenze settings are loaded automatically, thereby overwriting the parameter values loaded previously.

When does the problem occur?
When the card module is used to download a project, if the replacement device has a different power section from the device saved by the project.

Diagnostics options?
Following download with the card module, a PR0 error message is displayed. Resetting the error message automatically reloads the Lenze settings.

Short-term measures/recommendations?
Only use the card module to load parameter sets which have been read from a device of the same size.  

Evaluation:
The problem described here restricts the use of the card module for parameter transfer to exchanging parameters between devices of the same size.

CR Id: LDS00023113
Published with Service Message No. 2010/32