Touch probe TP1 (DI1) does not respond after mains switching and with CAN synchronisation (eliminated as of OPERATING SYSTEM V8.3)
Eliminated as of:
ECS Application OPERATING SYSTEM as of V8.3
Behaviour of the new version?
Touch probe function TP1 (DI1) is operational even when CAN synchronisation is active (C1120=1) and after mains switching.
Which products are affected?
ECS Application OPERATING SYSTEM <= V8.0
What happens?
Touch probe TP1 (DI1) for the digital frequency input (DFIn) is not detected.
When does the problem occur?
When CAN synchronisation is active (C1120=1) and after mains switching.
Diagnostics options?
The application does not respond to touch probe signals at digital input DI1.
Short-term measures/recommendations?
Write the configuration code for the touch probe C0428 = 1 after CAN synchronisation has been activated via C1120 or mains switching has been performed.
Evaluation:
The problem is detected during routine commissioning tests.
CR Id: LDS00024438, Failure Report Id:
CR Id: LDS00023583, Failure Report Id: 7048
Published with Service Message No. 2010/32