Index 0x1000 (device profile) is not updated with the 9400 Stateline

Eliminated from:
EtherCAT E94AYCET FV 2.00 communication module

Behaviour of the new version?
Index 0x1000 is displayed correctly with the 9400 Stateline / 9400 Highline using the DS 402 TA.



What is the reaction?
Index 1000 is read out by the EtherCAT master to identify the device profile. A device which includes the DS 402 application must have a value of 402 in its index. If the master reads out a value of zero, a DS402-compliant device is not detected and hence the relevant part from the xml device description is not loaded.

When does the problem occur?
When the EtherCAT master carries out an assignment of the xml device description by online bus scan.

Which products are affected?
EtherCAT E94AYCET FV 1.01 communication module with 9400 StateLine

Diagnostics options?
The above-described behaviour occurs if no DS402-compliant device is identified at the master end.

Short-term measures/recommendations?
None

Information taken from chapter 1.1.1 of Service Message No. 44/2009.