Rectified from:
Global Drive Oscilloscope V1.3.0.0
Behaviour of the new version?
With Global Drive Oscilloscope V1.3, the trigger responds when the specified value is reached.
What does the reaction look like?
The trigger of Global Drive Oscilloscope V1.2 does not respond when the specified value is reached.
When does the problem occur?
If a trigger value smaller than -65536 is entered in the Level field , Global Drive Oscilloscope causes the trigger to respond at a value that is 65536 greater than the trigger value.
Example:
If a trigger value of -100000 is entered in the Level field, the trigger responds at -34464.
Affects which products?
Global Drive Oscilloscope V1.2
Diagnostic possibilities?
None
Short-term measures/recommendations?
Do not enter any trigger values smaller than -65536.
Evaluation:
In the case of trigger values smaller than -65536, the trigger does not respond when the specified value is reached. Trigger values of this size tend to be entered infrequently.