Which products are affected?
HMI Designer V1.7 SP1
EPM-H410 (Graphical display unit)
EPM-H507 (Touch screen)
EPM-H510 (Touch screen)
Eliminated function restriction:
Thanks to the revision of the CAN driver, the update of the CAN process data is no longer frozen. The new CAN driver is loaded to the keypad by means of the HMI Designer. In order to support the new CAN driver the hardware of the devices EPM-H410, EPM-H507 and EPM-H510 needs to be changed. As a result, the device designations are changed as follows:
Old devices
Designation Material number
EPM-H410.1B.10 413183
EPM-H507.1A.10 13025987
EPM-H510.1A.10 413203
New devices
Designation Material number
EPM-H410.1C.10 13112270
EPM-H507.1B.10 13112305
EPM-H510.1B.10 13112306
The old CAN driver can be used in combination with both, the old and the new hardware.
The new CAN driver can only be used in combination with the new hardware. The corresponding driver can be assigned either by selecting the target hardware by choosing New under the Project selection tab or through the components in the project tree. As before, it is possible to convert from one software to another.