C0856 by factor 10000 too large

Which products are affected?
EVS93xx-EI (Servo PLC V6.x)
EVS93xx-ET (Servo PLC V6.x with technology function)
EPL-10200 (Drive PLC > V6.x)
ESP-GDC2 (Global Drive Control V4.9)
ESP-DDS2-x (Drive PLC Developer Studio V2.0 up to V2.2)

What happens?
For the three subcodes of code C0856 (DIS: AIF1_nInWx_a (input word x)) the Global Drive Control software (GDC) and the DDS Parameter Monitor (tab: Resources) indicate a value which is by factor 10000 too large.

When does the problem occur?
The response described before occurs whenever the three subcodes of code C0856 are read out by means of GDC or DDS.

Possible diagnostics?
Check the value of code C0856 by means of the EMZ9371 keypad.

Short-term measures/recommendations?
The function restriction has been eliminated with the current DDS version 2.3. An Update from version 2.x to V2.3 is provided in the Lenze Application Knowledge Base on the Internet.
In case of the GDC program use the application-specific device description generated with DDS V2.3 in order to monitor and change the codes. DDS generates the application-specific device description in the same directory in which the project file (*.pro) is located, too.

Evaluation:
In case of the display code C0856 GDC and DDS indicate a value which is by factor 10000 too large. This function restriction does not influence the data transfer via AIF interface.