Default setting under code C1121 does not correspond to the product documentation (remedied from B-SW V7.0)

Remedied from:
ECS axis module B-SW V7.0

Behaviour of new version?
After loading the default setting in the ECS axis module, code C1121 (Sync Cycle) indicates 2 ms which corresponds to the value mentioned in the Operating Instructions of the ECS axis module. The default setting value has been changed to 2 ms.



Which products are affected?
ECS axis module B-SW V6.7

What happens?
Contrary to the Operating Instructions code C1121 (Sync Cycle) indicates 10 ms instead of 2 ms after loading the default setting into the parameter set of the ECS axis module.

When does the problem occur?
Basically, code C1121 indicates 10 ms after loading the default setting.
However, this setting is only relevant if code C1120 (Sync mode) is set to a value unequal 0 (default setting for C1120 = 0).

Possible diagnostics?
Check the value under code C1122, e. g. by using the Global Drive Control software.

Short-term measures/recommendations?
Use e. g. the Global Drive Control software to set code C1121 to the value requested after loading the default setting.

Evaluation:
The default setting value for code C1121 does not correspond to the value mentioned in the documentation. Code C1121 is only relevant if cyclic and time controlled processes of the ECS axis module are to be started synchronously with other drive controllers. Code C1121 can be set manually to the value requested.

Published with service message No. 2006/14 and 2006/15