Forcing outputs in the states Pre-Operational and Operational

Function description
It is possible to force the outputs of the I/O systems IP20 by means of the parameter setting software Global Drive Control (set high), although the corresponding output is not yet triggered actively by the user program. This is executed in the file of the corresponding output module x in the index I6200h, subindex 00x.
In the index I2360h the forcing function can also be activated for the 'Pre-Operational' status (I2360h = 1: Forcing in Pre-Operational status is activated).
In the delivery status (default setting) the forcing in 'Pre-Operational' status is not activated.

Applications
The function for forcing outputs can be used during commissioning in order to test e. g. connected actors regarding the correct connection and function.