Ixt device temperature monitoring releases too early (OC5) (remedied from B-SW V6.5)
Remedied from:
ECS axis module B-SW V6.5
Behaviour of new version?
Irrespective of the setting under code C0173, the IxT device temperature monitoring does not release too early anymore (OC5).
Which products are affected?
ECS axis module B-SW V3.0
What happens?
The I*t device temperature monitoring releases too early (OC5).
When does the problem occur?
If C0173 ≥ 10 is set for adjusting the DC bus voltage threshold and as a result the LU threshold can be set variably via C0174.
Possible diagnostics?
None on the device itself. Check the utilisation, if necessary.
Short-term measures/recommendations?
Chose a selection with fixed LU threshold (C0173 ≤ 4).
Evaluation:
Not critical with regard to safety technology aspects. It will be possible to use a fixed LU threshold for most applications.
Published with service message No. 2004/26 and 2004/27