Fading-in function of the PID controller output

Which products are affected?

Application I/O ≤ SW 3.0

What happens?

Sudden speed change after controller enable

When does the problem occur?

The ramp function generator of the fading in function FADING is not reset by a controller enable but by mains connection.

Possible diagnostics?

Monitoring of the output frequency

Short-term measures/recommendations?

None.

Evaluation

Failure has been eliminated with software version 3.1.