Fixed as of:
PLC Designer V4.2
Behavior of the new version:
When an i550 inverter is added, the emergency telegrams are disabled in theEtherCAT parameters. As a result, no emergency telegrams are sent from the i550 slave to the EtherCAT master and, consequently, not to the Lenze Error Management of the Lenze controller.
Description of the behavior:
Error messages from the i550 inverter are also sent to the EtherCAT master as emergency telegrams.
Conditions under which the behavior occurs:
After being added to the PLC project, the i550 inverter is configured to send all error messages to the controller as emergency telegrams.
Affected products:
PLC Designer V4.0
Short-term measures, recommendations, assessment:
Set parameter 0x285C:010 (Alarm Suppression: Entry 10) of the i550 inverter to the value '0xFFFFFFFF'.
[Automatic Translation]