i950ES / i750ES / i750AS: Loading the factory setting does not affect parameter 0x28E8:01..02 "Diagnostic: Config. diagnostic value 1 & 2" (no change planned)

Removed from:
i950 Extended Safety (ES):   No change is currently planned.
i750 Extended Safety (ES):   Currently no change is planned.
i750 Advanced Safety (AS):   No change is currently planned.

Description of the behavior:
Executing the device command "Load default" (0x2022:01), results in the following parameters not for resetting to factory settings:

  • "Diagnosis: Config. Diagnostic value 1" - 0x28E8:01
  • "Diagnosis: Config. Diagnostic value 2" - 0x28E8:02    

Under what conditionsdoes the behavior occur?

  • The configuration of the diagnostic values 1+2 in the objects 0x28E8:01..02 are not parameterized equal to the factory setting. 
  • The device command "Load default" (0x2022:01) is executed or the "Reset device" button is pressed via the tool interface in the Easy-Starter.
Affected products: 
i950 Extended Safety (ES)
i750 Extended Safety (ES)
i750 Advanced Safety (AS)

Short-term measures / Assessment / recommendations:
The desired default values can be written 'manually' in 0x28E8:01 and 0x28E8:02. Athen the parameter set must be saved again in the device.


[Automatic Translation]
URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202500064/1/