Tab 'Firmware/Parameter set' not visible for i950 V1.8 + V1.9

Removed from:

Currently no fix is planned.




Description of behavior:

The tab Firmware/Parameters of an i950 EtherCAT slave of versions V01.08 and V01.09 is not displayed.  

 

Conditions under which the behavior occurs:

The i950 firmware supports a firmware download via FoE (File over EtherCAT) from version V01.08.00. 

i950: firmware download via FoE (File over EtherCAT) possible (from V01.08.00)

This function cannot be used if the dialog is not visible.

 
Affected products:
All versions of the PLC Designer; i950 CiA402 and TA CiA402 V01.08 + V01.09, Controller C5xx + C4xx

Short-term measures, Recommendations, Rating:
The tab Firmware/Parameters of an i950 EtherCAT slave is visible from version V01.10.

For all i950 EtherCAT slaves with a Lenze TA or TA user (0x4000 > 1) neither a firmware nor a parameter set download from the Lenze Motion Controller to the axis is supported.



[Automatic Translation]
URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202500204/1/
Contact form