Error LED of the c430 is on, no connection can be established (fixed with V1.13)

Corrected from: 
Cabinet Controller c430 V1.13
Behavior of the new version:
Booting the controller without SD card has no influence in establishing a connection with the controller.


Description of the behavior:

The error LED of the controller lights up red. It is not possible to establish a connection with the controller.

Conditions under which the behavior occurs:

If the controller is booted without an SD card, the behavior occurs after a total of 10 boot processes.

Affected products:

Cabinet Controller c430 from V1.11

Short-term measures, Recommendations, Rating:

  • Only switch on the controller c430 when an SD card is inserted in the controller.
  • Insert the SD card from another controller c430. Then restart the controller.
    After an internal boot process, the controller will restart normally.
    ATTENTION:
    The SD card must remain in the device otherwise the same behavior will occur again after 10 boot processes.
  • Using an empty SD card or pressing the reset button on the controller does not remove the functional restriction.
[Automatic Translation]
URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202400130/1/
Contact form