When selecting Imax (C00022) values higher than the maximum value of the inverter, C00022 will be limited to the maximum value (200% rated inverter current). No error message will occur.
In addition, C00022 will be limited at a fixed switching frequency of 16kHz (C00018) and 480V mains voltage (C00173).
What happens?
If values higher than the maximum value (higher than 200% rated inverter current) are selected in C00022 (Imax), the "Unknown error code AIF-Mode6" error message appears and the value is not accepted. When using the Engineer and access via CAN, C00022 can no longer be changed as a result (C00022 becomes invalid/red).
When does this behaviour occur?
The behaviour occurs when selecting Imax values > Irated