Recipe management: error message when loading recipes from device

Corrected from:
Cabinet Controller c520 V1.11
Cabinet Controller c550 V1.11
Servo inverter i950 V1.9

Behavior of the new version:
Recipes can be loaded without an error message if the following path was previously specified to save the recipe data in the 'RecipeManager' of the PLC Designer:
./PlcBootProject/Recipes

Description of the behavior:
The error message appears when uploading a recipe:
No recipe files with the extension xxx.csv were found in the runtime directory $IecFilePath$
Conditions under which the behavior occurs
The above error message can occur when uploading previously saved recipe data from the device.

Affected products:
Cabinet Controller c520 
Cabinet Controller c550 
Servo inverter i950 PLC (0x4000:0 = TA User [10000]

Short-term measure, recommendations, evaluation:
none

[Automatic Translation]


URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202300247/1/
Contact form