Boot application cannot be created after 'Reset origin device' (fixed with V1.13)

Corrected from:
Cabinet Controller c520 V1.13
Cabinet Controller c550 V1.13

Response of the new version:
After execution of the command 'Reset Origin [Device]' it is possible generate a boot application in the controller.

What happens?
When creating a boot application (command 'Online' > 'Create boot application for Lenze devices') the error message appears:
Error message when transferring the file

When does the behaviour occur?
A boot application can no longer be created online in the controller if the command 'Reset origin device [Device]' was previously executed with the checkbox 'PLC-Logic' activated.

Which products are affected?
Cabinet Controller c520 from V1.0
Cabinet Controller c550 from V1.0

Short-term measures:
When executing the command 'Reset origin device [Device]', do not activate the checkbox 'PLC logic'.
If you have already executed the command with the 'PLC Logic' checkbox activated, perform a mains switch of the controller. Afterwards, you can create a boot application online again.

Evaluation / recommendations:
With the command 'Reset origin device [Device]', the user administration, the PLC logic and the certificates on the controller can be deleted. After deleting the PLC logic, a boot application can only be created after the controller has been switched to mains. The command 'Reset Device Origin' can only be executed after it has been included in the menu via the 'Customise' dialogue.