Boot application with encrypted application not possible (no correction planned)

Corrected from:
It is no correction planned.

Response of the new version:
-
 
What happens? 
A boot application is created online with the PLC Designer. After switching the controller off and on again, the boot application does not start.
 
When does the behaviour occur? 
The behaviour occurs if the encryption technique 'Encryption with certificates' is set in the properties of the device tree object 'Application' in the tab 'Encryption'.
 
Which products are affected? 
Cabinet Controller c750 from V1.0
Cabinet Controller c300 from V3.8
Cabinet Controller 3200C from V3.0
Panel Controller p300 from V3.8
Panel Controller p500 from V3.2

Short-term measures: 
Do not use the 'Encryption with certificates' setting in the properties of the 'Application' object in the PLC project.
 
Evaluation / recommendations:
Encryption of the boot application with certificates is not supported by the Lenze controllers.

Automatic Translation

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202100400/1/