Hiperface DSL (OCT): Display under 0x2C4B:26 is not correct, depending on the selection of the display value under 0x2C4B:25

Corrected from:
Servo Inverter i950 FW: from V01.07.04.2313
 
Response of the new version:
The display under 0x2C4B:26 now works correctly. 
The setting sequence of the selection of the value to be displayed under 0x2C4B:25 no longer leads to the described behaviour.

 
What happens?
Hiperface DSL (OCT): The display parameter 0x2C4B:26 shows wrong values under certain conditions.

When does the behaviour occur?
The value to be displayed under 0x2C4B:26 is set under the corresponding selection parameter 0x2C4B:25.
If 0x2C4B:25 = "Lifetime [1]" is initially set and then another value to be displayed is selected, the behaviour described will occur.
 
Which products are affected?
Servo-Inverter i950 FW
 
Short-term measures / Evaluation / recommendations:  
When changing to a different display value under 0x2C4B:25, proceed as follows:
- First set 0x2C4B:25 = "No value [0]" and then 
- then set the desired display value under 0x2C4B:25.

Automatic Translation

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202100158/1/