Corrected from:
Cabinet Controller c300 from V3.21
Panel Controller p300 from V3.21
Response of the new version:
After switching on the controller, the error message described below no longer appears.
What happens?
After switching on the controller, the message appears:
Error: Evaluation of backup job failed. Please check configuration.
When does the behaviour occur?
The error message described above may occur if a firmware version 3.20 is installed in the controller and an SD card originating from a controller with an older firmware version is inserted and switched on.
Which products are affected?
Cabinet Controller c300 from V3.20
Panel Controller p300 from V3.20
Short-term measures:
Delete the following files and directories on the SD card and then switch the controller back on:
1. DeviceScanner
2. Management.db
3. ValueTables.db
Evaluation / recommendations:
When replacing the unit, the above error message may appear after switching on the Lenze controller. An application solution is described under Short-term measures.