Corrected from:
Cabinet Controller c520 V1.7
Cabinet Controller c550 V1.7
Cabinet Controller c750 V1.7
Response of the new version:
The error message 'Network: Invalid configuration' is only displayed if parameter 0x2859:003 is set to the value 'Error [1]' and an invalid PROFINET configuration is detected by the controller.
What happens?
After starting or restarting the c5x0 or c750 controller, the error message is displayed:
Network: Invalid configuration
The red LED of the controller lights up.
This error message must be acknowledged by the user.
When does the behaviour occur?
The error message occurs when the parameter 0x2859:003 (=PROFINET monitoring: Invalid configuration) is set to the value 'Error [1]' and thus deviates from the default setting 'Warning [2]'.
Which products are affected?
Cabinet Controller c520 from V1.0
Cabinet Controller c550 from V1.0
Cabinet Controller c750 from V1.0
Short-term measures:
Configure parameter 0x2859:003 to the value 'Warning [2]'.
Evaluation / recommendations:
When starting the controller, an error message appears regarding the PROFINET configuration, which remains pending until acknowledged, although the configuration is correct. The process data communication via PROFINET is not affected by this function restriction. An applicative solution is described under Short-term measure.
Automatic Translation