MQTT telegrams are not sent via PROFINET (corrected from V01.08.00)
Corrected from:
Servo Inverter i950 FW: from V01.08.00
Response of the new version:
MQTT telegrams are now sent via the applicatively parameterised PROFINET port, regardless of the IP configuration of the engineering port.
What happens?
MQTT telegrams are incorrectly not sent at all instead of being sent via the application-parameterised PROFINET interface.
When does the behaviour occur?
In the user application, an MQTT client is used in which "fb0" has been parameterised as the physical network interface so that the MQTT datagrams can be sent dedicatedly via PROFINET.
If the PROFINET port is both physically in the same network and logically in the same IP subnet as the engineering port, no MQTT datagrams are sent.
Set the IP configuration of the PROFINET port (Lenze parameter 0x2381:001..003) and the engineering port (Lenze parameter 0x2451:001..004) so that they are in different IP subnets.