Corrected from:
84TL V21.01
Response of the new version:
The error has been removed.
If two successive frequency data points have the same value one of the data points is ignored.
What happens?
If two successive frequency points have the same value (e.g. C967.010=40Hz and C967.011=40Hz), a division by 0 may occur in the freely definable characteristic (C06=10). As a result, the maximum voltage may be output by mistake.
What are the effects?
For the freely definable characteristic (C06=10), all entries for the frequency points (C967.xxx) must be different, otherwise there may be jumps in the output voltage.
Which products are affected?
8400 TopLine with a firmware < 21.01.00.00
Short-term measures:
None