Error message 103 at the backplane bus of the controller

What happens?
The following error message is reported:
I/O module msg. 103: Not all I/O modules are available (Master queue operation error).

When does the behaviour occur?
Many I/O modules are connected to the backplane bus of the controller.
As a result, more than 240 bytes of input or output are occupied in the process image.
  
Which products are affected?
Controller 3200C
Controller c300

Short-term measures:
Reduce the number of IO modules so that less than 240 bytes in the input image and 240 bytes in the output image are occupied.

Automatic Translation

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202000216/1/
Contact form