Analog input without dead band

Function extension:

When setting bit 11 in code C00143 to 1, for extended I/O and standard I/O, the dead band of the analog input will be set from 200mV and 40mV to 0V. After that, the analog input can be exactly scaled via code C00026 and C00027.

 

Contained in which products?

 

  • Inverter Drives 8400 motec


Application:
Using the analog input as a signal source.


URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/201900119/1/