V/f operation (VFC) and boost setting incorrectly too high: At output frequency zero, the current limiting controller (Imax) does not work sufficiently (corrected from V02.13.07)

Corrected from:
Servo Inverter i700, V1:   no repair planned for V1
Servo Inverter i700, V2:   from V02.13.07.12531
Response of the new version:
The boost voltage is now automatically adjusted within the device so that the maximum current limit (Imax) is maintained.

  
What happens?
At zero output frequency, the current limiting controller (Imax) does not work sufficiently well to keep the output current below the set Imax limit. 
 
When does the behaviour occur?
In V/f characteristic operation (VFC) and if the boost is incorrectly set too high.

Which products are affected?
Servo Inverter i700, V1
Servo Inverter i700, V2
 
Short-term measures / Evaluation / Recommendations:
Adjust the boost setting, i.e. set it smaller.
 
Automatic Translation

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/201900087/1/