Corrected from:
- 9400 HighLine V13.01.06
- 9400 Servo PLC V07.01.06
Response of the new version:
Correct status display in C388.
What happens?
The node guarding status displayed in C388 does not correspond to the actual slave status. Example: Although the connected slave is in the 'Operational' state, 'Pre-Operational' is indicated.
When does this behaviour occur?
This behaviour only occurs if C388 is used for slave status diagnostics.
Which products are affected? - 9400 HighLine < V13.01.06
- 9400 Servo PLC < V07.01.06
Short-term measures:
After executing CAN reset node, the status is displayed correctly, after mains switching an incorrect status is displayed.
Evaluation/recommendations:
Limited diagnostics options, no effects on the functionality of the device.