Corrected from:
Inverter Drives 8400 StateLine, HighLine, and TopLine from firmware version 14.00.00.00
Response of the new version?
SLVC: Motors with fd > 650 Hz (up to 1000 Hz) are now supported.
Which products are affected?
Inverter Drives 8400 StateLine, HighLine, and TopLine with a firmware version lower than 14.00.00.00
What happens?
Disconnection of the frequency inverter with OC1/OC11.
When does the problem occur?
SLVC control mode does not work if fd > 650Hz (OC1/OC11 when 650Hz are reached)
Short-term measures/recommendations?
None
Evaluation:
A motor with a base frequency fd> 650 Hz cannot be commissioned in SLVC control mode with FW< 14.00.00.00.