LS_DeviceMonitor: no hysteresis at the MctrlMotorTemp output
Which products are affected?
Inverter Drives 8400 TopLine with a firmware version from 14.00.00.00
Functional description
A hysteresis of 15K (fixed value) for the LS_DevicMonitor.MctrlMotorTemp function block output has been installed.
Like this, the output turns TRUE when the temperature set has been reached and FALSE again at a temperature less than the minimum temperature set minus 15K.