Function extension:
Now, the reset time of the field weakening controller can be set to maximally 26s (previously it could be set to maximally 6s). For this, the value range of C578 has been increased to 6200ms and an internal scaling has been implemented which will become effective if C578>6000ms.
Above 6000ms, the reset time internally effective will rise by 100ms every time the value is increased by 0.1ms.
Examples
C578 internally effective
6000.0ms -> 6000ms
6000,1ms-> 6100ms (6000ms + 1x100ms=6100ms)
6010.1ms-> 16100ms (6000ms + 101x100ms=16100ms)
Contained in which products?
- Inverter Drives 8400 HighLine V16.00.00
- Inverter Drives 8400 TopLine V16.00.00
Application:
Operation in the field weakening range with motors requiring a high reset time in the field weakening controller.