Visualisation does not show any current values (eliminated from V3.3.2)
Corrected from:
Controller 3200 C V3.3.2
Controller p500 V3.3.2
Behaviour of the new version?
The access of external visualisations is limited to 10 by the controller.
What happens?
Visualisation does not show any current values.
When does the problem occur?
The controller only supports the access of a maximum of three external visualisations. The fourth visualisation does not show any current values.
Which products are affected?
Controller 3200 C from V3.3
Controller p500 from V3.3
Diagnostics options?
None
Short-term measures/recommendations?
Limit the access to the controller to a maximum of 3 external visualisations.
Evaluation:
The controller supports a maximum of three external visualisations. If more visualisations are connected, they do not show any current values.
Taxonomy:
Controller 3221 C
,
Controller 3231 C
,
Controller 3241 C
,
Controller 3251 C
,
Controller 3200 C
,
Controller p500
AKB-ID:
201208256
Last update:
2023/09/09
Category:
Version Informations
Lenze reserves the right to change information on this page at any time. Any liability for the accuracy of the information is excluded.