Eliminated from:
9400 HighLine SW V10.00.12.00
9400 ServoPLC SW V04.00.12.00
Behaviour of the new version?
The evaluation of the speed recorded has been delayed, i.e. after switching on the drive controller it is waited for 40 ms before the speed recorded is also used for the monitoring function as described.
What happens?
When the device is switched on, the follow-up control of the resolver requires a certain time for the transient phenomenon. The transient phenomenon itself is already evaluated as resolver speed and causes incorrect activation of the monitoring function in C00576 'Speed monitoring tolerance' and the error response set in C00579 'Speed monitoring response' (although the motor is at standstill). The problem is restricted to machines which include resolvers. The error cannot occur if an encoder is used.
When does the problem occur?
The problem occurs when switching on the drive controller.
Which products are affected?
9400 HighLine SW ≤ V09.00.09.00
9400 ServoPLC SW ≤ V03.00.17.00
Possible diagnostics?
Unexpected error message.
Short-term measures/recommendations?
Switch the drive controller off and on again.
Evaluation:
The error occurs very rarely when the controller is switched on and can be avoided by applying the measures as described before.